| 参数 | 价值 |
|---|---|
| 230 V AC | |
| 出口 | 2 kV (Test Severity 3, Asymmetric) |
| 空调正常 | AcIn> 0.45 x ACN(ACN= 108 V AC) |
| 碰撞 | 18 ms, 30g, per direction in space (according to IEC 60068-2-27) |
| DC OK | UOUT> 0.9 x UN(UN= 24 V DC) |
| 深度 | 53 mm |
| 宽度 | 136 mm |
| 屈服 | Typ. 90% (120 V AC) |
| 颜色 | green |
| 高度 | 240 mm |
| 标记 | UL/C-UL Listed UL 61010-1 |
| 信号 | 2 kV (Test Severity 3, Asymmetric) |
| 默认 | closed |
| 数字的 | 30 V AC 30 V DC 100 mA |
| 紧张 | 10 V (Test Severity 3) |
| 降息 | > 40 °C ... 50 °C (1%/K) |
| 直径 | 5.6 mm |
| 入口 | 4 kV (Test Severity 3, Asymmetric) |
| 锁类型 | M12 Screw Lock |
| 频率 | 50 Hz |
| EN 61010-1 | III (≤ 2000 m) |
| 输入保险丝 | 6.3 A (internal (device protection)) |
| 上升时间 | ≤ 12 ms (UOUT(10 % ... 90 %)) |
| 标准 A | Normal service behavior within the specified limits. |
| 标准 B | Transient alteration of service behavior, which is corrected by the device itself. |
| 标准C | Temporary adverse effects on performance that are automatically corrected by the equipment or that can be reset by operating the control elements. |
| 观察 | Criterion A |
| 编纂 | s |
| 输入/输出 | asymmetric |
| 输出功率 | 240 W |
| 产品类型 | Power supply |
| 固定高度 | ≤ 4000 m (> 2000 m, Derating: 10%/1000 m) |
| 电压误差 | 70 % |
| 天气等级 | 4K26 (EN 60721-3-4) |
| 产品系列 | TRIO POWER |
| 连接时间 | < 1 sec |
| 连接类型 | M12 Cylindrical Connector |
| 频率范围 | 80 MHz ... 1 GHz |
| 杆数 | 3 |
| 残余涟漪 | ≤ 10 mVPP |
| 标牌类型 | LED |
| 房屋材料 | Metal |
| 阶段数 | 1,00 |
| 保护指数 | IP67 |
| 规则/条款 | IEC 61010-1 |
| 安装方式 | Wall Mounting |
| 调光偏差 | < 1% (static load change 10% ... 90 %) |
| 网络结构 | Star Network (TN, TT, IT (PE)) |
| 周期数 | 25 periods |
| 工作电压 | > 85 V AC |
| 状态指示 | 2 x Green LED |
| 交流频率范围 | 50 Hz ... 60 Hz ±10% |
| 电流吸收 | 2.3 A (120 V AC) |
| 断开电压 | < 85 V AC |
| 某种保护 | I |
| 保护电路 | Protection against transient overvoltages; Varistor |
| 污染程度 | 3 |
| 标识标牌 | AC OK |
| 下载 联系我们 | 6 kV (Test Severity 3) |
| 输入电压范围 | 120 V AC ... 240 V AC ±10% |
| 额定功率输入 | 285 VA |
| 振动(运行) | < 15 Hz, width ±2.5 mm (according to IEC 60068-2-6) |
| 频率范围(fN) | 50 Hz ... 60 Hz ±10% |
| 测试场强度 | 10 V/m (Test Severity 3) |
| 干扰发射 | Interference emission in accordance with EN 61000-6-3 (residential and commercial areas) and EN 61000-6-4 (industrial areas) |
| 低电压指令 | Compliance with the Low Voltage Directive 2014/35/EU |
| 静态增压降额 | > 40 °C ... 50 °C 1 %/K> 50 ... 60 °C 0.22 %/K (UN 230 V AC, PStat.Boost= PNx 1:25) |
| 涂有保护漆 | No |
| 超电流切断 | ≤ 25 A (typical) |
| 标称输出电压 | 24 V DC ±1% |
| 干扰电阻 | Immunity to interference according to EN 61000-6-1 (domestic use), EN 61000-6-2 (industrial use) |
| 耐短路 | Yes |
| 标准面值 | Electrical Safety |
| 再循环阻力 | ≤ 35 V DC |
| 标准/规范 | EN 61000-3-2 |
| 房屋建造 | Aluminum (AlMg3) |
| 接地分流电流(PE) | < 3.5 mA |
| 安装说明 | Stackable: horizontal 20 mm, vertical up 50 mm, vertical down 100 mm |
| 安装距离上下 | 50 mm / 100 mm |
| 额定输出电流(输入) | 10 A |
| 动态加速(IDyn.Boost) | 15 A (5 sec) |
| 平均故障间隔时间 (IEC 61709,SN 29500) | > 850000 h (25 °C) |
| 静态增益(IBoost 估计值) | 12.5 A (UN 230 V AC) |
| 最大介电强度 | ≤ 300 V AC 15 sec |
| 标称输入电压范围 | 120 V AC ... 240 V AC |
| 辐射杂散排放 | EN 55016 |
| 供电电压 电压类型 | AC |
| 可并联连接 | Yes, for redundancy and power boost |
| 左右安装距离 | 20 mm / 20 mm |
| 典型国家电网电压 | 120 V AC |
| 环境温度(服务) | -25 °C ... 60 °C |
| 电磁兼容性 | Compliance with EMC Directive 2014/30/EU |
| 浪涌电流积分 (I2t) | < 0.5 A2s |
| 网络故障桥接时间 | > 17 ms (120 V AC) |
| 输出浪涌保护 (OVP) | ≤ 30 V DC |
| 最大额定负载耗散 | < 25 W (120 V AC) |
| 输入/输出绝缘电压 | 3 kV AC (type test) |
| 最大开路功耗 | < 2 W (120 V AC) |
| 串联连接的可能性 | Yes |
| 传导干扰的发射 | EN 55016 |
| 允许的空气湿度(使用) | ≤ 100% (at 25°C, non-condensing) |
| 关闭电流电压限制 | Typ. 25 A (after 1 ms) |
| 环境温度(储存/运输) | -40 °C ... 85 °C |
| 最大允许空气湿度(使用) | ≤ 100% (at 25°C, non-condensing) |
| 根据 EN 55011 标准,无线电干扰 | EN 55011 (EN 55022) Class B Application in industry and residential |
| 环境温度(启动测试模型) | -40 °C |
| 选择合适的保险丝以实现防护等级保护 | 6 A ... 16 A (US/CAN: branch circuit protection |
| 无线电干扰电压符合 EN 55011 | EN 55011 (EN 55022) Class B Application in industry and residential |
| 根据 UL 94 标准划分的阻燃等级(外壳/端子) | V0 |
技术规格和性能数据
安装和操作指南