| 参数 | 价值 |
|---|---|
| Repeated strong short circuits can reduce the melting integral of the integrated safety fuse. | |
| EMC | to |
| 保险丝 | electronic |
| 深度 | 55.6 mm (With 7.5 mm rail) |
| 宽度 | 6.2 mm |
| 屈服 | > 98.5% |
| 高度 | ≤ 3000 m up to 52 °C (amsl) |
| 标记 | UL/C-UL Listed UL 508 |
| 紧张 | < 5V DC (Low State) |
| 湿度 | B |
| 材料 | PBT |
| 围栏 | to |
| 注射类型 | E (electronic) |
| 振动 | B |
| 观察 | Connection for the signal line tested according to EN 61000-4-4 with 1 kV; If applicable, protective measures should be provided on the client's side |
| 温度 | to |
| 建造 | Rail-mounted, one-piece module |
| 产品类型 | Appliance Protection Switches, Electronic |
| 脉冲长度 | ≥ 50 ms (High) |
| 电压降 | 0.28 V (with 0.5 A) |
| 湿度检查 | 96 h, 95% RH, 40 °C |
| 输出电流 | max. 0.015 A (Short Circuit Resistant) |
| 输出电压 | 24 V DC (Error) |
| 产品系列 | PTCB |
| 连接类型 | Push-in connection |
| LED通道关闭 | Off (Channel Off) |
| 标称电压 | 24 V DC |
| 杆数 | 1 |
| 红色LED通道 | Ignition (Channel Off, Overvoltage, or Active Undervoltage) |
| 尺寸方案 | |
| 耗散功率 | Typ. 0.1W (no load) |
| 保护指数 | IP20 |
| 额定电流输入 | 15 A DC (Total Input Current) |
| 规则/条款 | EN 61000-6-2 |
| 浪涌断开 | ≥ 30.5 V DC (active) |
| 安装方式 | Symmetrical rail: 35 mm |
| 故障安全元件 | 4 A DC |
| 绿色LED通道 | On (Channel Connected) |
| 工作电压 | 10 V DC ... 30 V DC |
| 需要预熔丝 | It is only necessary if IMaxof the power supply is > the ability to short circuit. Built-in safety feature. |
| 电流吸收 | Typ. 0.4 mA (with 24 V DC) |
| 断开连接时间 | ≤ 600 ms |
| 某种保护 | Iii |
| 通道数量 | 1 |
| 静息电流 I0 | Typ. 3.8 mA |
| 黄色LED通道 | flashes (Programming Mode On) |
| 污染程度 | 2 |
| 介电强度 | max. 35 V DC (Charging circuit) |
| 输入电压范围 | 7 V DC ... 30 V DC (Downside Reset) |
| (服役期间)事故 | 30g (IEC 60068-2-27, Ea test) |
| 最大容性负载 | 5.7 mF (Depending on current setting and available short-circuit current) |
| 温度降额 | 15 A (Total current at 60°C) |
| AWG导线段 | 24 ... 12 |
| 额定电流(预设值) | 0.5 A |
| 振动(运行中) | 10 Hz ... 59.6 Hz (Amplitude ±0.35 mm; according to IEC 60068-2-6, Fc test) |
| 主动电流限制 | Typ. 1.1 x IN |
| 测量容差 I | ± 7% |
| 刚性导体段 | 0.2 mm² ... 2.5 mm² |
| 欠压断开 | ≤ 9.2 V DC (active) |
| 再循环阻力 | max. 35 V DC |
| 待脱绝缘的长度 | 8 mm |
| 柔性导体段 | 0.2 mm² ... 2.5 mm² |
| 平均故障间隔时间 (IEC 61709,SN 29500) | 27129679 h (at 25°C at 21% load) |
| 模块初始化时间 | 40 ms |
| 环境温度(服务) | -30 °C ... 60 °C |
| 瞬态电压尺寸 | 0.5 kV |
| 短路击穿能力 | 300 A |
| 根据 UL 94 标准划分的阻燃等级 | V-0 |
| 断开通道后超时 | 5 sec (in overload/short circuit) |
| 环境温度(储存/运输) | -40 °C ... 70 °C |
| 带趾帽的柔性导线段,带塑料套管 | 0.25 mm² ... 2.5 mm² |
| 带趾帽的柔性导体段,无塑料套管 | 0.25 mm² ... 2.5 mm² |
技术规格和性能数据