| 参数 | 价值 |
|---|---|
| High demand | |
| 深度 | 114.5 mm |
| 震惊 | 15g |
| 宽度 | 12.5 mm |
| 高度 | 112.2 mm |
| 当前的 | max. 100 mA |
| 电压 | approx. 22 V DC (Us- 2 V) |
| 可插拔 | yes |
| CCCex 备注 | Use in potentially explosive areas is not permitted in China. |
| 继电器类型 | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
| 应用 | Safe switch off |
| 证书 | UL 22 ATEX 2912X |
| 指定 | A1/A2 |
| 过滤时间 | max. 2 ms (at A1-A2; test pulse width) |
| 输出保险丝 | 6 A gL/gG |
| 产品类型 | Coupling relay |
| 螺纹 | M3 |
| 组装说明 | See derating curve |
| 安装类型 | DIN rail mounting |
| 恢复时间 | 500 ms |
| 停止类别 | 0 |
| 鉴别 | II 3G Ex ec nC IIC T4 Gc |
| 浪涌电流 | typ. 400 mA (Δt s) |
| 产品系列 | PSRmini |
| 状态显示 | 2 x LED (green) |
| 颜色(外壳) | yellow (RAL 1018) |
| 文章修订 | 07 |
| 联系材料 | AgSnO2 |
| 错误指示 | 1 x LED (red) |
| 房屋材料 | Polyamide |
| 最大海拔 | ≤ 2000 m (Above sea level) |
| 输入数量 | 2 (Non-safety-related start inputs: Y1/Y2) |
| 剥皮长度 | 7 mm |
| 连接方式 | Screw connection |
| 安装位置 | vertical, horizontal, with front of module upward |
| 输出数量 | 2 (safety-related N/O contacts: 13/14, 23/24) |
| 平方总电流 | 60 A2(observe derating) |
| 开关电压 | min. 12 V AC/DC |
| 拧紧扭矩 | 0.5 Nm ... 0.6 Nm |
| 输出描述 | 2 NO contacts each in series, without delay, floating |
| 保护电路 | Serial protection against polarity reversal; 33 V suppressor diode |
| 交换容量 | min. 60 mW |
| 当前消耗 | < 5 mA |
| 申请须知 | Only for industrial use |
| 开关频率 | max. 0.5 Hz |
| 保护程度 | IP20 |
| 典型释放时间 | < 35 ms (when controlled via A1) |
| 标准/法规 | EN 60664-1, EN 60079-7, EN 60079-15 |
| 振动(操作) | 10 Hz ... 150 Hz, 2g |
| 触点开关类型 | 2 enabling current paths |
| 最大浪涌电流 | 500 mA (Δt = 1 ms at Us) |
| 正常运行模式 | 100% operating factor |
| 机械使用寿命 | 10x 106cycles |
| 美国电力消耗 | typ. 1.8 W |
| 额定绝缘电压 | 250 V AC |
| 短路保护 | no |
| 工作电压显示 | 1 x yellow LED |
| 类型。与我们一起开始的时间 | < 200 ms (when controlled via A1, automatic start) |
| 导线横截面 AWG | 24 ... 12 |
| 限制连续电流 | 6 A (High demand) |
| 安全完整性等级 (SIL) | 3 |
| 导体横截面刚性 | 0.2 mm² ... 2.5 mm² |
| 额定浪涌电压/绝缘 | Safe isolation, 6 kV reinforced insulation from control circuit, start circuit, signal output to the enabling current paths, 4 kV/basic insulation between the enabling current paths and between all current paths and housing |
| 环境温度(运行) | -40 °C ... 70 °C (observe derating) |
| 额定控制电源电流 IS | typ. 75 mA (depending on load M1 +100 mA) |
| 导体横截面可弯曲 | 0.2 mm² ... 2.5 mm² |
| 环境温度(储存/运输) | -40 °C ... 85 °C |
| 额定控制电路供电电压(美国) | 20.4 V DC ... 26.4 V DC |
| 机构场所的最低保护程度 | IP54 |
| 输入/启动和反馈电路的电压 | 24 V DC -15 %; +10 % |
| 最大允许湿度(储存/运输) | 75 % (on average, 85% infrequently, non-condensing) |
| 最大允许总导体电阻 | 150 Ω |
| 最大允许相对湿度(运行) | 75 % (on average, 85% infrequently, non-condensing) |
| 额定工况下的最大功率耗散 | 5.5 W (IL² = 60 A²) |
| 开关容量符合IEC 60947-5-1标准 | 4 A (24 V (DC13)) |
技术规格和性能数据
安装和操作指南