| 参数 | 价值 |
|---|---|
| For DC see load limit curve, e.g., the following values: | |
| 类型 | block modular |
| 深度 | 54 mm |
| 宽度 | 53.6 mm |
| 高度 | 126.1 mm |
| 电流消耗 | max. 280 mA (all relays pick up) |
| 产品类型 | I/O component |
| 安装类型 | DIN rail mounting |
| 产品系列 | Axioline F |
| 供电电压 | 5 V DC (via bus base module) |
| 连接名称 | Axioline F connector |
| 文章修订 | 02 |
| 污染程度 | 2 |
| 剥皮长度 | 8 mm |
| 连接方式 | Bus base module |
| 安装位置 | any (observe temperature and current derating) |
| 输出数量 | 4 (floating) |
| 交付范围 | including bus base module and Axioline F connectors |
| 开关电流 | max. 8 A AC (cos phi = 1) |
| 输入地址区域 | 0 Byte |
| 尺寸说明 | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
| 交换容量 | max. 2000 VA |
| 传动速度 | 100 Mbps |
| 尺寸图 | |
| 申请须知 | Only for industrial use |
| 输出地址区域 | 1 Byte |
| 开关频率 | max. 6 (per minute) |
| 保护程度 | IP20 |
| 接口数量 | 2 |
| 过电压类别 | III (EN 61010-2-201/UL 61010-2-201), up to 2000 m above sea levelII (EN 61010-2-201/UL 61010-2-201), up to 3000 m above sea level |
| 标准名称 | Ambient conditions |
| 连接技术 | 2-conductor |
| 触点开关类型 | N/O contact |
| 机械使用寿命 | 10x 106cycles |
| 所需参数数据 | 1 Byte |
| 气压(运行) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| 标准/规范 | IEC 61850-3 |
| 导体横截面 AWG | 24 ... 16 |
| 所需配置数据 | 6 Byte |
| 导体横截面刚性 | 0.2 mm² ... 1.5 mm² |
| 连接方式说明 | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.When selecting the cables, please note that in the case of a small conductor cross section and high current, the terminal point temperature may be up to 30 K above the ambient temperature. |
| 刚性导体横截面 | 0.2 mm² ... 1.5 mm² |
| 环境温度(运行) | -25 °C ... 60 °C (max. 6 A/channel for wall mounting on horizontal DIN rail; max. 4 A/channel for any mounting position) |
| 气压(储存/运输) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| 导体横截面可弯曲 | 0.2 mm² ... 1.5 mm² |
| 允许湿度(运行) | 5 % ... 95 % (non-condensing) |
| 柔性导体横截面 | 0.2 mm² ... 1.5 mm² |
| 测试电压:继电器触点/逻辑 | 4 kV |
| 环境温度(储存/运输) | -40 °C ... 85 °C |
| 允许湿度(储存/运输) | 5 % ... 95 % (non-condensing) |
| 额定工况下的最大功率耗散 | 1.4 W |
| 测试电压:继电器触点/功能接地 | 4 kV |
| 开关容量符合IEC 60947-5-1标准 | 6 A (120 V (AC15)) |
| 测试电压:继电器触点/继电器触点(开路触点) | 1 kV, 50 Hz, 1 min. |
| 测试电压:继电器触点/继电器触点(相邻公连接器) | 2.5 kV |