| 参数 | 价值 |
|---|---|
| GTIN | 4046356763554 |
| 订单密钥 | 2701503 |
| (供应) | max. 2 A (at UA(IO-Link B ports, pin 2 and pin 5)) |
| 产品目录页 | Page 203 (C-6-2017) |
| 深度(注) | 30.5 mm |
| 包装单元 | 1 pc |
| 宽度(注) | 60 mm |
| 身高(注) | 185 mm |
| (IO-Link 输入) | Short-circuit protection |
| 原产地 | DE (Germany) |
| (数字输出) | 24 V supply (actuator supply)/FE 500 V AC 50 Hz 1 min. |
| 海关关税编号 | 85176200 |
| 职称(通用) | PROFIBUS DP |
| (电气隔离) | Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g |
| 指定(接口) | PROFIBUS DP |
| 钻孔间距(注) | 198.5 mm |
| 频道数量(总览) | 2 |
| 尺寸说明(注) | The height is 212 mm including fixing clips. |
| 尺寸图(注) | |
| 端口类型(数字输入) | Class A |
| 连接方式(通用) | M12 fast connection technology |
| 设备类型(接口) | PROFIBUS slave |
| 保护类型(供应) | Overload protection |
| (标准和法规) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| 传动速度(一般) | 9.6 kbps ... 12 Mbps (Automatic baud rate detection) |
| 职位数量(一般) | 5 |
| 信号延迟(IO-Link 输入) | max. 150 µs (when switched on) |
| (IO-Link端口的供应) | Short-circuit protection for the sensor supply |
| 测试部分(数字输出) | 24 V supply (communications power and sensor supply, IO-Link ports)/bus connection 500 V AC 50 Hz 1 min. |
| 传输物理学(总论) | PROFIBUS-DP-compliant copper cable |
| 净重(常温常压) | 552 g |
| 切换速率(IO-Link 输入) | 1 per second, maximum (at nominal inductive load) |
| 端口数量(数字输入) | 4 |
| 地址区域分配(常规) | 1 ... 126, adjustable |
| 防护等级(尺寸) | IP65/IP67 |
| 允许的电缆长度(供货) | < 20 m |
| 连接方式(数字输入) | M12 fast connection technology |
| 连接方式(IO-Link 输入) | M12 connector, X01 ... X04 have double occupancy |
| 安装类型(环境条件) | Wall mounting |
| 输出数量(IO-Link 输入) | max. 8 |
| 输出描述(IO-Link 输入) | IO-Link ports in digital output (DO) mode |
| 保护类型(IO-Link 输入) | Overload protection |
| 标称负载,欧姆负载(IO-Link 输入) | 3.6 W (160 Ω, at nominal load) |
| 单件重量(不含包装) | 552.000 g |
| 气压(运行)(尺寸) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| 房屋材料(环境条件) | Pocan® |
| 中国RoHS(标准和法规) | Environmentally Friendly Use Period = 25; |
| 连接技术(数字输入) | 3-wire |
| 连接技术(IO-Link 输入) | 3-wire |
| 指定连接点(通用) | Copper cable |
| 系统特定协议(接口) | PROFIBUS protocols DP V1 |
| 过载时的行为(IO-Link 输入) | Shutdown with automatic restart |
| 机械测试(电气隔离) | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
| 标称输出电压(IO-Link 输入) | 24 V DC |
| I/O 电源的标称电压(电源) | 24 V DC |
| 连接方式说明(一般) | B-coded |
| 防护等级(电气隔离) | III, IEC 61140, EN 61140, VDE 0140-1 |
| 输入名称(IO-Link端口的供电) | Digital inputs at pin 2 for type A ports |
| 标称负载,感性(IO-Link 输入) | 3.6 VA (0.8 H, 160 Ω, at nominal load) |
| 环境温度(操作)(尺寸) | -25 °C ... 60 °C |
| 气压(储存/运输)(尺寸) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| 输入频率(IO-Link端口的供电) | 0.5 kHz |
| 允许湿度(运行)(尺寸) | 5 % ... 95 % |
| 使用限制(关键商业数据) | 1 |
| 标识(母线耦合器的系统限制) | Actuators (UA) |
| 输入数量(IO-Link端口供应) | max. 8 (EN 61131-2 type 1) |
| 连接方式(IO-Link端口的供电) | M12 connector, X01 ... X04 have double occupancy |
| 输入滤波时间(IO-Link端口供电) | < 1000 µs |
| 每个 IO-Link 端口的标称电流(电源) | max. 150 mA (at C/Q (pin 4), maximum of 1.6 A over all 8 IO-Link C/Q and L+ cables) |
| 保护类型(IO-Link端口供电) | Overload protection |
| 关闭时的输出电流(IO-Link 输入) | max. 300 µA |
| 关闭时的输出电压(IO-Link 输入) | max. 1 V |
| 供电电压(母线耦合器系统限制) | 24 V DC |
| 每个设备的最大输出电流(IO-Link 输入) | 1.2 A |
| 总传感器电流(IO-Link端口供电) | max. 1.6 A (from L+/L-) |
| 连接技术(IO-Link端口的供应) | 3-wire |
| 每通道最大输出电流(IO-Link 输入) | 150 mA |
| 标称输入电流(IO-Link端口供电) | typ. 3 mA |
| 环境温度(储存/运输)(尺寸) | -25 °C ... 85 °C |
| 连接方式(母线耦合器的系统限制) | M12 connector (T-coded) |
| 允许湿度(储存/运输)(尺寸) | 5 % ... 95 % |
| 当前功耗(母线耦合器系统限制) | typ. 30 mA ±15 % (at 24 V DC) |
| 输入描述(IO-Link端口供电) | IO-Link ports in digital input (DI) mode |
| 位置数量(总线耦合器系统限制) | 4 |
| 标称输入电压 UIN(IO-Link 端口的供电) | 24 V DC |
| 每个通道的传感器电流(IO-Link 端口的供电) | max. 200 mA (from L+/L-) |
| UIN 处的标称输入电流(IO-Link 端口的供电) | typ. 3 mA |
| 输入电压范围“0”信号(IO-Link端口供电) | -0.3 V DC ... 5 V DC |
| 输入电压范围“1”信号(IO-Link端口供电) | 15 V DC ... 30 V DC |
| 额定供电电压范围(母线耦合器系统限制) | 18 V DC ... 31.2 V DC (including all tolerances, including ripple) |
| 限制电路中断时感应电压(IO-Link 输入) | -15 V DC |
技术规格和性能数据